AVR MX341
Regular Price:
$90.50
On Sale For:
$82.36
In stock
AVR-MX341This product qualifies for quantity discount pricing.
| Quantity | Discount |
|---|---|
| 3-6 | 3% |
| 7-10 | 7% |
| 11-500 | 11% |
| Sensing Input | Voltage 190~264 VAC 1 phase 2 wire Frequency 50/60 Hz selectable |
|---|---|
| Power Input(PMG) | Voltage 140~220 VAC 3 phase 3 wire Current 3A / phase Frequency 100~120 Hz nominal |
| Output | Voltage Max. 120 VDC Current Continuous 2.7A, Intermittent 6A for 10 sec. Resistance Min. 15 Ohm |
| Voltage Regulation | < ±1% (with 4% engine governing) |
| Voltage Build-up | Residual volts at AVR terminal > 5 VAC |
| External Volts Adjustment | ±10% with 1 K Ohm 1 watt trimmer |
| Unit Power Dissipation | Max. 12 watt |
| Thermal Drift | 0.05% per °C change in AVR ambient |
| Soft Start Ramp Time | 3 sec. |
| Analogue Input | Max. input ±5 VDC Sensitivity 1V for 5% generator volts Input Resistance 1 K Ohm |
| Droop Input | Burden 10 Ohm Max. sensitivity 0.07A for 5% droop (PF=0) Max. input 0.33A |
| Under Frequency Protection (Factory Setting) |
Set point 95% Hz Slope 170% down to 30 Hz |
| Current Limit Input | Burden 10 Ohm Sensitivity Range 0.5~1A |
| Over Voltage Detector Input | Set point 300V Time delay 1 sec. (fixed) CB trip coil volts 10~30 VDC / 0.5 Amp |
| Over Excitation Protection | Set point 90 VDC Time delay 10 sec. (fixed) |
| Environment | Operating Temperature : -40~70 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 3.3G @ 100~2 KHz |
| AVR Controls Functions | VOLT : Voltage Adjustment STAB : Stability Adjustment U/F : UFRO Knee point Set DROOP : Droop Adjustment TRIM : Analogue Input Adjustment EXC TRIP : Over Excitation Level Set DIP : U/V Rate Set |
| Dimensions | 150.0 (L) x 135.0 (W) x 48.0 (H) mm |
| Weight | 394g ±2% |